ANTSPACE HK3(with DWT-T)

Short Description:


Product Detail

Product Tags

Specifications

Specification Details For ANTSPACE HK3

Product Overview  
Model ANTSPACE HK3
Dimensions (L*W*H) (mm) 6058*2438*2896
Miner Capacity 210 units -S19 Hyd. Series miner
Container Certification China Classification Society Certification
Safety Certification North America/Standards:NFPA 79:2021,UL 508A:2018 R8.21,
CSA C22.2 No. 14-18,ANSI/ISO 12100:2012
EU/Standards:EN ISO 12100,EN 60204-1
Operating Power(kW) 1047~1050
PUE(Power Usage Effectiveness) 1.022(Excluding cooling tower)/1.036(Including cooling tower)
Input Voltage and Frequency 415V±5% 60Hz(North America)
400V±5% 50Hz(EU、Middle East)

 

Detailed Characteristics  
Shipping Weight(T) 8
Operating Weight (T) 12
Main Switch of Power Distribution Cabinets(A) 1200(North America)
1250(EU、Middle East)
Rated Current(A) 952
Standard Power(kW) 1049
Maximum Power(kW) 1050
Rated Current per Miner(A) 10
Inlet Cable The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:
L1 single core cable 600kcMil(300mm²)x4
L2 single core cable 600kcMil(300mm²)x4
L3 single core cable 600kcMil(300mm²)x4
N Single-core cable 600kcMil(300mm²)x4
PE single-core cable 500kcMil(240mm²)x2
Connection Interface(Cooling Tower) DN125(GB/T 9119-2010 PN16 DN125)
Connection Interface(Plate Heat Exchage Interface) DN100(GB/T 9119-2010 PN16 DN100)
Flow Rate(m³/h) >85
Quantity of ANTSPACE powered by one 2500kVA Transformer 2

Specification Details For Dry-Wet Towers

One of the following two Dry-Wet Towers can be chosen based on the personalized demand.

Product Overview  
Type Dry-Wet Tower Traditional Type (DWT-T) Dry-Wet Tower Container Type (DWT-C)
Dimensions(L*W*H)(mm) 5800*2240*4200 6058*2438*2896
Heat Dissipation Capacity(kW) 1000 1000
Outlet Temperature @ 28℃ Wet Bulb Temperature 35℃ 35℃
Container Certification None China Classification Society Certification
Safety Certification North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21,
CSA C22.2 No. 14-18, ANSI/ISO 12100:2012
EU Standards: EN ISO 12100, EN 60204-1
North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21,
CSA C22.2 No. 14-18, ANSI/ISO 12100:2012
EU Standards: EN ISO 12100, EN 60204-1
Operating Power(kW) 14~28 14~28
Motor Rated Voltage and Frequency 415V±5% 60Hz(North America)
400V±5% 50Hz(EU、Middle East)
415V±5% 60Hz(North America)
400V±5% 50Hz(EU、Middle East)

 

Detailed Characteristics  
Shipping Weight(T) 5 7
Operating Weight(T) 9 12
Connection Interface(Container) DN125(GB/T 9119-2010 PN16 DN125) DN125(GB/T 9119-2010 PN16 DN125)
Water Resupply Pipe Interface DN40(Internal thread) DN40(Internal thread)
Drain Pipe Interface DN65(Internal thread) DN65(Internal thread)
Noise Level @25℃, 16m 70dBA 70dBA
Water Consumption(m³/h) 1~1.5 1~1.5

Environmental Requirementss

Environmental Requirements
1 Cooling tower is required to be placed on flat ground, horizontal degree (±1 degree).
2 The ground surfaced is required to be hardened and stable, able to withstand at least 14-ton load.
3 A 10-ton crane is needed for unloading ANTSPACE and cooling tower.
4 Add-on items such as stairs, transformers, cables, bridge racks and cable distribution boxes are not included in the delivery of ANTSPACE. BITMAIN team can provide design suggestions if needed.
5 Client needs to confirm the opening directon of container and it needs to face air-intake. Door on left is current design by defult.
6 Keep at least 2 meters of air in-take space around the cooling tower.
7 Altitude: ≤3000m. If the altitude is higher than 1000-meter, transformer and switch should be derated, the total power of ANTSPACE must be decreased by 1% for each elevation increment of 100 meters.
8 Operating temperature: -25°C to 40°C. Operating humidity: 10%RH to 90%RH. When the initial coolant temperature is below 20 °C, the internal circulation should be turned on to heat up the coolant to above 20 °C before starting the mining machine.
9 When the ambient temperature is below 5 ℃, the cooling tower can be switched to cold-dry mode.
10 Choose pure water or suitable antifreeze as coolant based on local climate conditions.
11 The suitable ambient temperature for ANTSPACE does not represent the suitable ambient temperature for mining machine.

 

NOTES

 

1. The ANTSPACE HK3 is recommended to be used simultaneously with The ANTMINER S19 Pro+ Hyd.

2. The pictures shown are for reference only; the final shipment version shall prevail.


  • Previous:
  • Next:

  • Related Products

    S19